Three Phase Digital Voltmeter AMC96L-AV3(AMC72L-AV3)
description1
description2
General
AMC series programmable intelligent meters,adopting AC sampling technology,can directly or indirectly measure electric voltage and current of single phase or three phase grid. It can be used for local display,and connecting industrial control device to form measuring control system.
Detail



Product Parameter
Technical Parameter |
Value |
||
Input |
Rated value |
Voltage: AC100V,400V,660V(only AMC96L type); current: AC1A or 5A |
|
Overload |
Voltage: 1.2 times rated value(continuous) 2 times rated value(1 second) Current: 1.2 times rated value(continuous) 10 times rated value (1 second) |
||
Frequency |
45Hz~65Hz |
||
Power consumption |
<0.5VA |
||
Accuracy |
Class 0.5 |
||
Funct ion |
Display |
LED or LCD |
|
Communication |
RS485(Modbus-RTU) |
||
Alarm |
1 channel passive relay,contact capacity 3A/30VDC, 3A/250VAC |
||
Analog output |
DC4~20mA( load < 500Ω) |
||
Switching |
Input |
4 channels or 2 channels passive contact Input |
|
Output |
2 channels switching output, NO relay contact, capacity 3A/30VDC, 3A/250VAC |
||
Auxiliary power supply |
Voltage range |
AC/DC 85~265V |
|
Power consumption |
<5VA |
||
Insulation resistance |
≥100MΩ |
||
Environment |
Temperature |
Operating:-10°C~+55°C Storage: -25°C ~+70°C |
|
Humidity |
≤93%(no condensation) |
||
Altitude |
≤2500m |
||
Dimension

| Shape | Panel | Housing | Cut out | ||||
| Unit:mm | Width | Height | Width | Height | Depth | Width | Height |
| 48 Square | 49 | 49 | 44 | 44 | 93 | 45 | 45 |
| 72 Square | 75 | 75 | 66.5 | 66.5 | 94.3 | 67 | 67 |
| 96 Square | 96 | 96 | 86.5 | 86.5 | 77.8 | 88 | 88 |
Wiring

AC Voltage Signal (400V or 660V AC L-L) Input via direct Connection (3-phase 4-wire)

AC Voltage Signal (400V or 660V AC L-L) Input direct Connection (3-phase 3-wire)

AC Voltage Signal (100V AC L-L) Input via -/100V AC PTs (3-phase 4-wire)

AC Voltage Signal (100V AC L-L) Input via -/100V AC PTs (3-phase 3-wire)
Installation
Diagram
Application
Packing&delivery

Product Selection
| Type | Basic function | Shape | Optiona function |
| AMC48-AI AMC48-AV |
Current,voltage measurement; LED |
48 Square | RS485 communication(/C) Analog output(/M) |
| AMC48-AI3 AMC48-AV3 |
None | ||
| AMC48L-AI AMC48L-AV |
Current,voltage measurement; LCD |
1.RS485 communication(/C) 2.Analog output(/M) |
|
| AMC48L-AI3 AMC48L-AV3 |
None | ||
| AMC72-AI AMC72-AV AMC72-AI3 AMC72-AV3 |
Current,voltage measurement; LED |
72 Square | 1.RS485 communication(/C) 2.Analog output(/M) 3.Alarmoutput(J) 4.Analog output +RS485 communication(MC) 5.RS485 communication +switching output 2DI2DO(/KC) 6.Alarm output +analog output +RS485 communication(JMC) |
| AMC72-DI AMC72-DV |
DC voltage,current measurement; LED |
||
| AMC72L-AI AMC72L-AV AMC72L-AI3 AMC72L-AV3 |
Current,voltage measurement; LCD |
||
| AMC72L-DI AMC72L-DV |
DC voltage,current measurement; LCD |
||
| AMC96-AI AMC96-AV AMC96-AI3 AMC96-AV3 |
Current,voltage measurement LED |
96 Square | 1.RS485 communication(/C) 2.Analog output(/M or/3M) 3.Alarm output(/J) 4.Analog output +RS485 communication(/MC or/M3C) 5.RS485 communication +switching 4DI2DO (/KC) 6.Alarm output+analog output +RS485 communication(JMC) |
| AMC96L-AI AMC96L-AV AMC96L-Al3 AMC96L-AV3 |
Current,voltagemeasurement; LCD |
||
|
Note:1.AI/AV means single-phase current/voltage,Al3/AV3 means three-phase current/voltage; 2./Jmeans 1 channel relay output(multiplexing with second channel switching output) | |||