Precision Distribution Monitoring Solution for IDC
Application
Structure



Function
1. Incoming line and outgoing line circuits independent monitoring modules.
2. Can measure up to 2 incoming line circuits and up to 192 outgoing line circuits current, voltage, power, energy and power quality.
3. Data centralized monitoring and display by HMI and data is uploaded to power and environment monitoring system through RS485.
4. For high voltage DC 240V or 336V system, insulation monitoring module can be added to monitor ground insulation resistance of main bus.
5. DC24V power supply for touch screen and outgoing line monitoring module(power supply from main module output ).
6. Communication:monitoring device by RS485, touch screen by RS485 or RJ45.
7. Certificate:CE.
Product Selection
Product name |
Product image | Functions |
ATP007kt ATP010kt touch screen |
|
● 7 or 10 inch touch screen |
| AMC16Z-ZA data center AC incoming line monitoring device |
|
● Designed specifically for the power supply management of server in the data center ● Measure A+B independent 2 channels three-phase inlet ● U, I, P, Q, S, PF, kWh, kvarh ● 2-63rd harmonic ● RS485, Modbus-RTU communication ● CE certification ● Din rail 35mm installation |
| AMC16Z-FAK24 data center AC outgoing line monitoring device |
|
● Designed specifically for the power supply management of server in the data center ● Power supply by AMC16Z-ZA ● Measure A+B independent 24 circuits ● U, I, P, Q, S, PF, kWh, kvarh ● 2-31st Harmonic ● RS485, Modbus-RTU communication ● Din rail 35mm installation |
| AMC16Z-FAK48 data center AC outgoing line monitoring device |
|
● Designed specifically for the power supply management of server in the data center ● Measure A+B independent 48 circuits ● Power supply by AMC16Z-ZA ● U, I, P, Q, S, PF, kWh, kvarh ● 2-31st Harmonic ● RS485, Modbus-RTU communication ● Din rail 35mm installation |
| AMC16Z-ZD data center DC incoming line monitoring device |
|
● Designed specifically for the power supply management of server in the data center ● Measure A+B independent inlet circuit ● U, I, P, Q, S, PF, kWh, kvarh ● RS485, Modbus-RTU communication ● CE certification ● Din rail 35mm installation |
| AMC16Z-FDK24 data center DC outgoing line monitoring device |
|
● Designed specifically for the power supply management of server in the data center ● Power supply by AMC16Z-ZD ● Measure A+B independent 24 circuits ● RS485, Modbus-RTU communication ● Din rail 35mm installation ● CE certification |
| AMC16Z-FDK48 data center DC outgoing line monitoring device |
|
● Designed specifically for the power supply management of server in the data center ● Power supply by AMC16Z-ZD ● Measure A+B independent 48 circuits ● Power supply by AMC16Z-ZD ● RS485, Modbus-RTU communication ● Din rail 35mm installation ● CE certification |
| AKH-0.66/W AC outgoing line current transformer |
|
● Current ratio:100A/50mA ● Common Specification:100A/50mA |
| AHKC-BS DC outgoing line hall effect current sensor |
|
● Current ratio:100A/5V ● Common Specification:100A/5V |
Diagram

Human Machine Interface

Photo on Site