Medical Isolation Power Supply System
Solutions

Medical Isolation Power Supply System

2024-08-19

Application

Medical IT system insulation monitoring device and fault location system is suitable for hospital operating room, ICU (CCU) and other important places, and can provide a safe place for such continuous, reliable power solutions.

Medical IT electrical system definition

Low-voltage power distribution grounding and neutral connection systems are divided into three basic forms: IT, TT, and TN. TN is divided into three derivative types: TN-C, TN-S, and TN-C-S.

Solution for PV DC coupled energy storage

15u6

The first letter indicates the status of the neutral point and ground of the power supply:

T - indicates that the neutral wire of the power supply is directly grounded; 

I - indicates that the neutral wire of the power supply is not grounded or grounded with high impedance;

The second letter indicates the state of the load side and ground;

T - The leaking conductive part of the electrical device is directly grounded, and the grounding point is independent of the grounding point of the power supply terminal; 

N - The exposed conductive part of the electrical device is directly electrically connected to the grounding point of the power supply terminal; 

The third letter C indicates that the neutral line (N line) is shared with the protective zero line (PE line); the fourth letter S indicates that the neutral line (N line) is separated from the PE line

Why need the IT system for hospital?

faaf2i8e

TN-S system:poor power supply safety and continuity

1. In the grounding system, when a live wire grounding fault occurs, the neutral wire is short circuited to ground, the circuit breaker trips, and the continuity of power supply is affected.

2. Any electrical equipment powered by the TN system will generate a certain amount of leakage, which poses a threat to medical personnel and patients.

3. If the leakage current of the equipment exceeds the operating current of the leakage current protection circuit breaker, the circuit breaker will trip, which also affects the continuity of power supply.

faaf3ql2

IT system:good power supply safety and continuity

1. The IT system is not grounded. When any live wire is grounded (the first grounding fault), the insulation monitoring device reports a grounding fault, but the circuit breaker will not trip, and the system can continue to operate with the fault.

2. Due to the system not being grounded, leakage current forms a loop through the distributed capacitance of the system. Under high capacitance impedance, the leakage current will be relatively small, and the normal system leakage current is below microamperes.

3. For medical IT systems, IEC standards require that the input and output circuit breakers of the IT system must not have overload protection function and must not be powered off when overloaded.

Structure

structurerk9

Product Selection

Product name

Product image

Functions

AITR medical isolation transformer

 AITRg9z

Isolating transformers for medical IT systems

Double insulation treatment, Electrostatic shielding layer

PT100 temperature sensor

Rated power: 3.15-10kVA

AIM-M300 medical isolation monitor  AIM-M300hiw Auxiliary Power Supply: DC 18~36V

Resistance Measuring Range: 15~999kΩ

Response Time: ≤3s

Thermal Resistor: 2 Pt100

AID150 medical isolation monitoring alarm and display device  AID150tm5 Auxiliary Power Supply: DC 24V

Number of IT Systems Monitored: 16

Insulation Resistance Alarm Setting: 10~999kΩ

Alarm Mode: Sound-light alarm

Communication: RS485, Modbus-RTU

ASG150 medical isolation signal generator  ASG1503m1 Auxiliary Power Supply: DC 24V

Rated Voltage: AC 0~242V  

Rated Frequency: 45~60Hz

Communication: CAN

AKH-0.66P26 current transformer  AKH-0p9z The maximum measurable current is 6, Current ratio 2000:1

Work with the AIM-M300 series insulation monitoring device to measure the load current of the isolation transformer

ACLP10-24 medical DC power supply  ACLP10-24gag Power Supply to AID series

AC 220V input, DC 24V output

Completely Isolated Linear Transformer