Medical Isolation Power Distribution Cabinet GGF
General
The GGF series isolation power cabinet is suitable for the power distribution system of the medical 2 class place or other IT systems, such as clean operation room, ICU/CCU intensive care unit, and emergency room. These places have high requirements on the reliability and security of the power supply system, so IT is necessary to use local IT system for power supply and implement local auxiliary measures. According to the different conditions of the operating room and intensive care unit, the corresponding power distribution scheme is provided.
The GGF series isolation power cabinet adopts the cabinet color that is relatively coordinated with the medical place, making it consistent with the overall environment of the medical place. The power cabinet can be installed in three ways, namely ground installation, embedded wall installation and split installation, which can be flexibly selected according to the site conditions.
The GGF series isolation power cabinets meet the standards of IEC 61439-2 Low-voltage switch gear and control gear assemblies - Part 2: Power switch gear and control gear assemblies and IEC 60364-7-710:2021 Low-voltage electrical installations - Part 7-710: Requirements for special installations or locations - Medical locations.
The GGF series isolation power cabinet complies with the enterprise standard Q31/0114000129C009 The GGF series Medical Isolation Power Cabinet.
Model Description

Feature



Product Parameter
| Technical parameters | GGF-IXG | GGF-IXQ | GGF-IXF | GGF-OXG | GGF-OXQ | GGF-OXF |
| Rated voltage | 220V AC | 380V/220V AC | ||||
| Rated capacity | 3.15/5/6.3/8/10 | —— | 3.15/5/6.3/8/10 | —— | ||
| Rated frequency | 50/60Hz | |||||
| Distribution circuit | IT system: 4 or 5 channels AC 220V(can be customized) | IT system: 8 channels AC 220V(can be customized) | ||||
| —— | TN-S systems: 1 AC 380V, 8 AC 220V | |||||
| IP level | IP31 | IP34D | IP31 | IP34D | ||
| Installation | Grounded | Embedded | Grounded | Embedded | ||
| Inlet and outlet line | Bottom inlet and bottom outlet | Both bottom and top have access lines | Bottom inlet and bottom outlet | Both bottom and top have access lines | ||
| Communication | RS485, MODBUS-RTU | |||||
Dimension(unit:mm)

Wiring

GGF-I8G Isolation Distribution Cabinet System Diagram

GGF-O8G Isolation Distribution Cabinet System Diagram
Application