Medical Insulation Test Signal Generator ASG150
General
The ASG150 test signal generator adopts 32-bit microprocessor chip and high-precision signal generation circuit to realize the generation of specific test signal. When the monitored IT system has insulation faults, it can start up and produce test signal in time, working with the insulation fault locator to realize insulation fault location.
Feature



Product Parameter
| Auxiliary power supply | Voltage | DC 24V |
| Power consumption | 2VA | |
| Monitored system | Rated voltage | 0~242V AC |
| Frequency | 45~60Hz | |
| Location signals | Location voltage | <25V |
| Location current | <1mA | |
| Fault location | Maximum channels | 4 |
| Response time | <2s | |
| Communication | Bus | CAN |
| Protocol | Custom protocol |
Dimension(unit:mm)

Wiring
Upper terminal: 24V and G are auxiliary power supply, L1 and L2 are connected with monitored it system (parallel connection can be made to output terminal of isolation transformer);
Lower terminal: PE is connected to equipotential terminal block on site, H and L are can communication terminals (connect with AIM-200 and AIL150).


Application