Leave Your Message
BM200 Series Explosion-proof Signal Isolation Barrier
Analog Signal Isolator

BM200 Series Explosion-proof Signal Isolation Barrier

Input type: Current/Voltage/Thermal resistance Pt100/Resistance/Thermocouple

Transmission accuracy: 0.2%

Input: 0~20mA /4~20mA ,0~5V /0~10V /1~5V  (Distribution voltage: 12V/20mA) PT100 /0~10K

Output: 0~20mA /4~20mA , 0~5V /1~5V , 0~10V 

Power Supply: 20~35V DC

Response Time: 5ms to reach 90% of final value

Installation: DIN Rail

Standard&Certificate: CE

    description1

    description2

    General

    BM200 series isolated safety barrier can transmit signals between the safe area and the dangerous area, and limit the energy transfer from the safe area to the dangerous area caused by the fault. The voltage, current, temperature, resistance signals generated by the equipment (transmitter) on the dangerous side are isolated and converted into corresponding linear voltage and current signals outputting to the safe area. The product requires independent power supply, and the input/output/power supply is isolated. It can be used in current source, two-wire, three-wire transmitter equipment. 

    Model description

    model description8o2

    Technical Parameter

    Channel type

    Single-way input and single-way output, single-way input and double-way output, double-way input and double-way output

    Input type Current/Voltage/Thermal resistance Pt100/Resistance/Thermocouple
    Input signal 0~20mA /4~20mA 0~5V /0~10V /1~5V (Distribution voltage: 12V/20mA) PT100 /0~10K/K 、E 、T 、J 、N 、R 、S 、B
    Output signal 0~20mA /4~20mA (Safe side input); Load resistance: ≤550Ω 0~5V /1~5V (Safe side input); Load resistance: ≥330K 0~10V (Safe side input); Load resistance: ≥500K
    Transmission accuracy 0.2%
    Temperature modulus 50ppm/℃ (The output signal is current)
    Response time 5ms to reach 90% of final value (RTD Pt100/resistance/thermocouple input: 1s to reach 90% of final value)
    Power supply 20~35V DC
    Work temperature -20℃~+60℃
    Fix mode Rail installation
    Dielectric strength Intrinsically Safe and Non-Intrinsically Safe ≥2500VAC; Power supply and Non-Intrinsically Safe ≥500VAC Note: Intrinsically Safe is input, Non-Intrinsically is output

    Dimension

    Product category Type of products Outline dimension
    BM200 BM200-□□/□-B11(single-way input and single-way output) 99mm*114.5mm*12.5mm
    BM200-□□/□-C□2 (single-way input and double-way output/double-way input and single-way output) 99mm*114.5mm*22.5mm

    BM200-□□/□-B11 outline dimension(unit:mm)

    dimension-1qyq

    BM200-□□/□-C□2 outline dimension(unit:mm)

    dimension-2v4n