AKH-0.66K-Φ mA Output Split Core Current Transformer for Cable
General
The appearance is nice and the installation and wiring are convenient. AKH-0.66/K-Φ series split current transformers are mainly used in reconstructing projects of urban and rural power grids. Product has the advantages of small size, high accuracy, strong load capacity, easy installation, etc.They save the manpower, material resources and financial resources and improve the efficiency of users.
Model Description

Feature

Product Parameter
| Type | Ratio(A) | Class&Burden(VA/Ω) | Turns | Dia(mm) | |
| Class 0.5 | Class 1 | ||||
| K-Φ10 | 5A/1.67mA | 10 | 1 | 10 | |
| 5A/2.5mA | 10 | 1 | 10 | ||
| 10A/5mA | 10 | 1 | 10 | ||
| 40-50A/20mA | 10 | 1 | 10 | ||
| 80A/26.7mA | 10 | 1 | 10 | ||
| K-Φ16 | 120A/40mA | 10 | 1 | 16 | |
| 40-100A/20mA | 10 | 1 | 16 | ||
| 80A/32mA | 10 | 1 | 16 | ||
| K-Φ24 | 60-200A/20mA | 10 | 1 | 24 | |
| 200A/40mA | 10 | 1 | 24 | ||
| K-Φ36 | 400A/50mA | 10 | 1 | 36 | |
| 400A/40mA | 10 | 1 | 36 | ||
| 600A/75mA | 10 | 1 | 36 | ||
| 200-400A/20mA | 10 | 1 | 36 | ||
Spec. and size(unit:mm)

| Type | Outline size | Through size | Tolerance | |||||
| W | H | D | M | N |
Φ1 |
Φ2 |
||
| K-Φ10 | 27 | 40 | 26 | 24 | 36 | 10 | 9 | ±1 |
| K-Φ16 | 31 | 50 | 29 | 28 | 42 | 16 | 17 | |
| K-Φ24 | 39 | 71 | 46 | 36 | 52 | 24 | 23.5 | |
| K-Φ36 | 42.5 | 82 | 58 | 40 | 56 | 33.5 | 35 | |
Technical indicators
Rated operation voltage: AC 0.66kV
Rated frequency: 50~60Hz
Ambient air temperature: -30℃~70℃
Height above sea level: ≤3000m
Power frequency withstand voltage: 3000v/1min 50Hz
Used in place without direct rain and snow, without severe pollution and acute shock
Installation

Application